Low-profile trays: waste depth under the floor

Published

Low profile shower tray installation: find room for the trap under the floor, support the tray fully, keep access to the waste, test the flow and then seal.

A low profile tray saves step height by leaving no space beneath itself, so the trap and waste pipe normally go into the floor. Before ordering, confirm there is room below for the trap body, a falling pipe route to the drain and a way to reach the joint later. Without all three, choose a raised tray.

Measure the floor void

On a timber floor, lift a board where it is safe and measure:

  • the depth below the board surface to the ceiling or ground beneath;
  • joist direction, spacing and position relative to the tray waste;
  • any cables or pipes in the same space;
  • the distance and height difference to the existing waste connection.

Do not notch or drill joists to make a pipe fit without competent structural advice. A waste hole that lands on a joist may mean turning the tray, moving it or choosing another outlet position. In flats, the floor may include fire and sound protection that belongs to the building, so ask the managing agent.

On a solid floor, a channel for the waste is building work. Check the construction, damp protection and services before anyone cuts into it.

Trap and pipe sizes

Approved Document H gives a shower trap of 40 mm with a 50 mm water seal, and allows the seal to be no less than 38 mm where the appliance discharges directly to a gully. Shallow traps exist for tight spaces, so compare the stated seal depth and flow rate, not just the height. The same document sets an unventilated bath branch at up to 3 m in 40 mm pipe or 4 m in 50 mm; ask how your shower run compares.

Mira's fitting guide explains that a low-profile tray has no space for pipework underneath, so part of the floorboards must be removed. It advises a floor that does not move, using marine plywood over 20 mm thick where boards need replacing, and cutting an access hatch beside the tray.

Prepare the base

The support must be level, firm, dry and clean. Mira's installation guide for its Flight trays shows bedding on a 5:1 sand and cement mix at least 10 mm thick, or a construction adhesive that suits the floor, applied under all contact points. Other trays require their own bed, and some forbid certain adhesives. Never leave a thin tray bridging gaps.

  1. Dry fit the tray against the finished walls.
  2. Mark the waste position and cut the opening to the trap maker's size.
  3. Assemble and connect the pipe so its fall is set before the tray goes down.
  4. Check the route for joints you will not be able to reach.

Fit the waste and test early

Follow the waste maker's seals. The Mira sheet says not to use silicone on the waste fitting and warns against overtightening it. It also recommends pouring water into the tray to check drainage before final fixing and tiling, and states that flow into that tray must not exceed 25 litres per minute. Compare your shower's flow with your own tray and waste figures, especially for large overhead heads.

Test with the shower running or with several buckets. Look below for drips and check that water does not stand around the waste.

Level, seal and finish

Use a spirit level along every edge and diagonally. The fall is built into most trays, so tilting one can trap water in a corner. Let the bed set for the time given before standing in it. Wall tiles or panels come down onto the tray, with the sealant applied as the instructions describe. Floor finishes should not block the access point.

Electrics and waterproofing

Moving a shower into a new position or adding lighting brings electrical rules into play, and tanking the walls is its own job. Settle who does each before the old tray leaves.

If you are not able to open the floor safely, or the drain route is unknown, explain that in the contact form and email photos of the room, the existing waste and any access underneath. For a base that has to be bedded over concrete, see trays on a solid floor.

Questions people ask

Can a low profile tray sit on any floor?

Only where the waste and pipe can go below it with adequate fall. Otherwise a raised installation is needed.

Do I need access to the waste?

Yes. Mira's tray instructions say to position the tray so the waste is easily accessible for maintenance.